Exams > 2022 JPM Sim-d — Respond to RCP Standpipe Low Level Alarm

2022 JPM Sim-d — Respond to RCP Standpipe Low Level Alarm

⚠️ DRAFT
JPM Sim-d — Respond to RCP Standpipe Low Level Alarm Sim | RO/SRO | 003 A1.10 (2.5/2.7)
Location: Simulator
Time-Critical: No
Alternate Path: No
Estimated Time: 6 minutes

Initial Conditions:
- Unit 2 is at 100% power.
- No major equipment is out of service and no Tech Specs are active.

Initiating Cue:
- You are the Reactor Operator.
- Respond to all alarms and indications.
- Your evaluator will respond to all alarms not related to your task.
Task Standard:
Upon receipt of a RCP standpipe low level alarm, the operator aligns valves to fill the standpipe with primary water, and terminates the fill when the high level alarm is received.
▶ Show Critical Steps & Key Actions
Step Critical Element Standard
CUE 21 RCP standpipe low console alarm illuminates Operator reports standpipe level low console alarm for 21 RCP.
1.0 Review CAUSES per S2.OP-AR.ZZ-0011 Reads likely causes: low seal flow across #2 seal, excessive flow through #3 seal.
3.1 Determine if standpipe low level AND seal water leakoff flow alarm occur together Determines no seal leakoff flow alarm is concurrent with standpipe level low — marks step N/A (does NOT go to AB.RCP-0001).
3.2.A If required, START 21 or 22 Primary Water Pump Selects one Primary Water pump in Manual and depresses START PB. (Conditional — fill can be done without starting PW pump, but fill takes longer.)
3.2.B * OPEN 2WR80, PW TO CONTMT STOP V Depresses OPEN PB for 2WR80 on 2CC2 console (PRT bezels) and verifies OPEN PB illuminates.
3.2.D * OPEN 21WR62, Standpipe Supply Valve for 21 RCP Depresses the OPEN PB for 21WR62 on 21 RCP bezel and verifies OPEN PB illuminates.
3.3.A * When hi level alarm received: STOP the Primary Water Pump Depresses STOP PB for running Primary Water pump (if previously started) and verifies STOP PB illuminates.
3.3.B * CLOSE 2WR80, PW TO CONTMT STOP V Depresses CLOSED PB for 2WR80 and verifies CLOSED PB illuminates.
3.3.C * CLOSE 21WR62, Standpipe Supply Valve Depresses CLOSED PB for 21WR62 and verifies CLOSED PB illuminates.
Key Decision Point:
Step 3.1 is the discriminating step. The applicant must evaluate whether the standpipe low level alarm is accompanied by a concurrent seal water leakoff flow alarm. If BOTH alarms are present, the applicant must transition to AB.RCP-0001 (RCP Abnormality) indicating a potential seal problem. In this JPM, only the standpipe low level alarm is present (caused by #3 seal leak), so the correct action is to continue with the standpipe fill procedure rather than entering the AB.
Ref: S2.OP-AR.ZZ-0011 (Rev 63) | Task: N0020160101 | K/A: 003 A1.10 — Ability to predict and/or monitor changes in parameters associated with operating the RCPS controls: Standpipe level (2.5/2.7) | Safety Fn: 4-Pri | Source: Bank | View JPM PDF