procedures > S2.OP-SO.125-0004 — 125VDC Ground Detection

S2.OP-SO.125-0004 — 125VDC Ground Detection

⚠️ DRAFT

S2.OP-SO.125-0004 — 125VDC Ground Detection

⚠️ DRAFT — Reconstructed from exam materials

Purpose

Provides guidance for detecting and isolating grounds on the 125VDC electrical distribution system on Salem Unit 2.

Key Information

Ground Detection Criteria

IndicationMeaning
Resistance ≤ 50K ohmsGround IS detected
Resistance > 50K ohmsNormal — no ground present

Isolation Method

  • Open breakers on the bus ONE AT A TIME
  • Evaluate ground readings after each breaker is opened
  • Leave breaker open if ground clears (resistance rises above 50K ohms)
Exam — 2023 Q46
A 125VDC bus ground ohmmeter reading of 40K ohms indicates a ground IS detected (less than 50K ohms threshold). Per S2.OP-SO.125-0004, breakers are opened one at a time until resistance indicates greater than 50K ohms.