procedures > S2.OP-SO.PZR-0010 — Pressurizer Backup Heaters Power Supply Transfer

S2.OP-SO.PZR-0010 — Pressurizer Backup Heaters Power Supply Transfer

⚠️ DRAFT

S2.OP-SO.PZR-0010 — Pressurizer Backup Heaters Power Supply Transfer

Purpose

Provides direction for transferring the pressurizer backup heater groups between their normal power supply (4KV Group Bus) and emergency power supply (460V Vital Bus). Used during loss of offsite power events to restore pressurizer heaters from the emergency diesel generator-backed vital buses.

Key Actions / Information

Section 5.3 — Transfer to Emergency Power Supply

JPM — 2022 IP-i
Transfer of 22 Backup Group PZR heaters to emergency power (2A 460V Vital Bus) requires: verify 2AX1AX14X is OPEN, direct NCO to place 22 B/U Group in MANUAL and press OFF pushbutton, verify 2EX1EP2EPX is OPEN, remove interlock key from 2EX1EP2EPX, place 11 of 14 disconnects in OFF (only 3 remain ON to limit load within emergency bus capacity), place 2EP PZR HTR BUS EMERGENCY FEED DISCONNECT SWITCH in ON using JAM key to unlock, then insert interlock key and UNLOCK breaker 2AX1AX14X. This limits heater load to 3 of 14 heater groups to stay within the 460V Vital Bus capacity.
Exam — 2020 Q11
Procedural caution: "Aligning pressurizer heaters to vital bus adds approximately 210 KW to bus load". Maximum diesel generator load is 2750 KW (2000 hr rating). To add PZR heaters without exceeding the 2000 hr limit, current DG loading must be adjusted to no greater than 2750 - 210 = 2540 KW.