procedures > S2.OP-AR.ZZ-0002 — Overhead Annunciators Window B

S2.OP-AR.ZZ-0002 — Overhead Annunciators Window B

⚠️ DRAFT

S2.OP-AR.ZZ-0002 — Overhead Annunciators Window B

Purpose

Provides alarm response procedures for Unit 2 Overhead Annunciator Window B alarms, including DC bus voltage, service water header pressures, and other B-panel alarms.

Key Actions / Information

Exam — 2020 Q13
OHA B-2, "2A 125 VDC CNTRL BUS VOLT LO": On loss of 2A Vital 125 VDC Bus (0 VDC on 2RP9), the only affected equipment from the listed malfunctions is 2A EDG is NOT available for start. #1 SGFP Emergency Oil Pump and Main Turbine Emergency Oil Pump are powered from other DC bus segments (250 VDC or 28 VDC), not the 2A 125 VDC bus.