S2.OP-AR.ZZ-0012 — Console Alarm Response
⚠️ DRAFT — Reconstructed from exam materials
Purpose
Provides alarm response guidance for console alarms on Salem Unit 2, including the URGENT FAILURE alarm for the rod control system.
Key Alarms
URGENT FAILURE
- All rod motion is inhibited in BOTH Manual and Automatic
- Rods are held in position by the stationary gripper coil energized at reduced current
- Moveable gripper coil is de-energized
Exam — 2023 Q55
Per S2.OP-AR.ZZ-0012, an Urgent Failure alarm prevents all rod motion in Manual or Automatic. Rods are held in position by the stationary gripper coil energized at reduced current. Moveable gripper coil is de-energized.
LOSS OF TRIPPING CAPABILITY (Bezel 4-17)
- Indicates loss of power to the shunt trip coil for the affected RTB
- Shunt coil is energized to trip — without power it cannot initiate a trip
- UV (undervoltage) coil is de-energized to trip — it remains functional
- 2CC2 RTB pushbuttons ONLY energize the shunt trip coil — they are non-functional when shunt coil power is lost
Exam — 2020 Q38
"LOSS OF TRIPPING CAPABILITY" alarm on RTB "A": the shunt trip coil will NOT be capable of opening RTB "A" because the alarm indicates loss of power to the shunt coil. UV trip coil remains functional (it de-energizes to trip). 2CC2 pushbuttons ONLY energize the shunt coil — with shunt coil power lost, they cannot trip the RTB.
PRIMARY WATER FLOW DEVIATION
Exam — 2018 Q31
Primary Water Flow Deviation Alarm setpoint: ±5.0 gpm above the setpoint. Boric Acid Flow Deviation alarm setpoint is ±0.8 gpm — common distractor.
Exam — 2019 Q3
Primary Water Flow Deviation Alarm setpoint: ±5.0 gpm above the setpoint. Boric Acid Flow Deviation alarm setpoint is ±0.8 gpm — do not confuse the two deviation alarm setpoints.
Connections
- Related systems: RPS/SSPS, Rx Vessel & Internals, CVCS
- Related exam questions: 2018 Q31, 2019 Q3, 2023 Q55, 2020 Q38
- Related exam: 2018 NRC Written Exam, 2019 NRC Written Exam, 2023 NRC Written Exam, 2020 NRC Written Exam