procedures > S2.OP-AR.DG-0001 — EDG Alarm Response

S2.OP-AR.DG-0001 — EDG Alarm Response

⚠️ DRAFT

S2.OP-AR.DG-0001 — EDG Alarm Response

Purpose

Provides alarm response guidance for Emergency Diesel Generator alarms, including lube oil pressure, temperature, and trip alarms.

Key Actions / Information

Exam — 2019 Q79
EDG Engine Lube Oil Header Low Pressure trip setpoint: EDG trips when lube oil header pressure FIRST lowers below 40 psig. Trap: the EDG ENGINE LUBE OIL HEADER LOW PRESSURE ALARM actuates at 60 psig — this is the alarm, not the trip. The trip occurs at 40 psig, 20 psi below the alarm.