SALEM
SALEM STUDY SYSTEM
Tech Specs > TS 3/4.3 — Instrumentation

TS 3/4.3 — Instrumentation

⚠️ DRAFT

TS 3/4.3 — Instrumentation

3/4.3.1 — Reactor Trip System Instrumentation

LCO 3.3.1.1
The Reactor Trip System instrumentation channels and interlocks shown in Table 3.3-1 shall be OPERABLE with RESPONSE TIMES as shown in Table 3.3-2.

Applicability: As shown for each functional unit in Table 3.3-1

Reactor Trip Setpoints (Table 2.2-1)

#Functional UnitTrip SetpointAllowable Value
1Manual Reactor TripN/AN/A
2Power Range Neutron Flux (Low)25% RTP≤26% RTP
2Power Range Neutron Flux (High)109% RTP≤110% RTP
3Power Range High Positive Rate5% RTP (τ ≥ 2 sec)≤5.5% RTP
5Intermediate Range Neutron Flux25% RTP≤38.5% RTP
6Source Range Neutron Flux10⁵ cps≤1.44 x 10⁵ cps
7Overtemperature Delta-TSee Note 1See Note 3
8Overpower Delta-TSee Note 2See Note 4
9Pressurizer Pressure — Low1865 psig≥1855 psig
10Pressurizer Pressure — High2385 psig≤2395 psig
11Pressurizer Water Level — High92% of instrument span≤93%
12Loss of Flow90% of design flow per loop*≥89%
13SG Water Level — Low-Low14.0% NR span≥13.0% NR span
15Undervoltage — RCPs2900 volts each bus≥2850 volts
16Underfrequency — RCPs56.5 Hz each bus≥56.4 Hz
17ATurbine Trip — Low Auto Stop Oil45 psig≥45 psig
17BTurbine Trip — Stop Valve Closure15% off full open≤15%

Design flow is 82500 gpm per loop. (TS Table 2.2-1, Amendment No. 310)

Minimum Channels OPERABLE (Table 3.3-1, Selected Functions)

FunctionTotal ChannelsChannels to TripMin OPERABLEApplicable Modes
Power Range Neutron Flux (High)4231, 2
Power Range Neutron Flux (Low)4231, 2
Intermediate Range Neutron Flux2111, 2
Source Range Neutron Flux2113, 4, 5
Overtemperature Delta-T4231, 2
Overpower Delta-T4231, 2
Pressurizer Pressure — Low4231, 2
Pressurizer Pressure — High4231, 2
Pressurizer Water Level — High3221
Loss of Flow (per loop)3/loop2/loop2/loop1
SG Water Level Lo-Lo (per SG)3/SG2/SG2/SG1, 2
Undervoltage — RCPs1/bus1/bus x 21/bus x 21
Underfrequency — RCPs1/bus1/bus x 21/bus x 21
Turbine Trip (Auto Stop Oil)3221
▶ Bases — 3/4.3.1 RTS Instrumentation
Bases — 3/4.3.1

OPERABILITY Requirements

The OPERABILITY of the protective instrumentation systems and interlocks ensures that: (1) the associated reactor trip will be initiated when the parameter monitored by each channel or combination thereof exceeds its setpoint, (2) the specified coincidence logic and sufficient redundancy is maintained to permit a channel to be out of service for testing or maintenance consistent with maintaining an appropriate level of reliability, and (3) sufficient system functional capability is available from diverse parameters. The integrated operation of each of these systems is consistent with the assumptions used in the accident analyses.

Trip Setpoint Methodology

Trip Setpoints are the nominal values at which the bistables are set. Any bistable is considered properly adjusted when the “as-left” value is within the band for CHANNEL CALIBRATION accuracy (rack calibration + comparator setting accuracy). The Trip Setpoints are based on the analytical limits stated in the UFSAR. To allow for calibration tolerances, instrumentation uncertainties, instrument drift, and severe environment errors for RPS channels that must function in harsh environments as defined by 10 CFR 50.49, the Trip Setpoints and Allowable Values are conservatively adjusted with respect to the analytical limits. The methodology is consistent with ISA-S67.04-1982, endorsed via NRC Regulatory Guide 1.105, Rev. 2.

The actual nominal Trip Setpoint entered into the bistable is more conservative than the Allowable Value to account for changes in random measurement errors detectable by a CHANNEL FUNCTIONAL TEST (e.g., drift during the surveillance interval). If the measured setpoint does not exceed the Allowable Value, the bistable is considered OPERABLE. All known uncertainties are factored into each Trip Setpoint determination.

TSTF-493 Footnotes (Table 4.3-1, Functional Units 5 and 6)

The as-found tolerance is calculated using square root sum of the squares (SRSS) combination of rack calibration accuracy, rack M&TE accuracy, rack comparator setting accuracy, and rack drift. The as-left tolerance uses the same SRSS method but excludes drift. If the as-found setting is outside its tolerance but conservative with respect to the Allowable Value, a channel performance evaluation is required before returning to service. If the as-left setting cannot be returned to within tolerance of the nominal Trip Setpoint, the channel shall be declared inoperable.

Surveillance and Testing

Surveillance and maintenance outage times are determined per WCAP-10271 and supplements. WCAP-14333-P-A, Rev. 1 and WCAP-15376-P-A, Rev. 1 provide the risk-informed basis for increased completion times, bypass test times, and surveillance test intervals for RTS and ESFAS.

Channel testing in a bypassed condition shall be performed without lifting leads or jumpering bistables. For Power Range Neutron Flux CHANNEL CALIBRATION in Modes 1 and 2 (Note 17), the SSPS input relays are excluded when the installed bypass test capability is used, to reduce the potential for inadvertent reactor trip. The SSPS input relays must be included at least once every 18 months. The same exclusion applies to CHANNEL FUNCTIONAL TEST for Power Range Neutron Flux and High Positive Rate (Note 18).

Response Time Verification

Response time verification provides assurance that reactor trip actuation is completed within the time assumed in the safety analysis. Response time acceptance criteria have been relocated to UFSAR Section 7.2 tables and 7.3 tables. Response time may be verified by actual response time tests (sequential, overlapping, or total channel measurements) or by summation of allocated sensor response times with actual tests on the remainder of the channel. WCAP-13632-P-A, Rev. 2 provides the basis for using allocated sensor response times for specific sensors. The allocation must be verified prior to placing a component in service and re-verified after maintenance that may adversely affect response time.

Intermediate Range Neutron Flux Trip

The IR trip provides protection against uncontrolled RCCA bank rod withdrawal from a subcritical condition during startup, providing redundant protection to the Power Range Neutron Flux Low Setting trip. In Mode 1 below P-10 and in Mode 2 above P-6, the IR trip must be OPERABLE. Above P-10, the PR High Setpoint provides protection. Below P-6 in Mode 2, the Source Range trip provides protection. In Modes 3, 4, or 5, the IR trip is not required because control rods must be fully inserted and only shutdown rods may be withdrawn.

Action times: one inoperable IR channel allows 24 hours for a slow, controlled power adjustment above P-10 or below P-6. If both IR channels are inoperable between P-6 and P-10, immediately suspend positive reactivity additions and reduce power below P-6 within 2 hours.

Source Range Neutron Flux Trip

In Mode 2 below P-6, two OPERABLE SR channels ensure no single random failure disables the trip. If one SR channel is inoperable in Mode 2, immediately suspend positive reactivity additions. If both SR channels are inoperable, the RTBs must be immediately opened. In Modes 3, 4, and 5 with RTBs closed and CRDS capable of rod withdrawal, one inoperable SR channel requires restoration within 48 hours or all rods fully inserted and CRDS incapable of rod withdrawal within the next hour. If both SR channels are inoperable, RTBs must be immediately opened. With RTBs open and CRDS incapable of rod withdrawal, the SR channels provide flux monitoring only.

(TS Bases B 3/4 3-1 through B 3/4 3-1c, Amendment Nos. 294, 306, 316, 321)


3/4.3.2 — ESF Actuation System Instrumentation

LCO 3.3.2.1
The ESFAS instrumentation channels and interlocks shown in Table 3.3-3 shall be OPERABLE with their trip setpoints set consistent with the values shown in Table 3.3-4.

ESF Actuation Setpoints (Table 3.3-4) — Complete

1. Safety Injection

Functional UnitTrip SetpointAllowable ValueSource
Manual InitiationN/AN/ATS T3.3-4
Automatic Actuation LogicN/AN/ATS T3.3-4
Containment Pressure — High4.0 psig≥4.5 psigTS T3.3-4
Pressurizer Pressure — Low1765 psig≤1755 psigTS T3.3-4
Differential Pressure Between Steam Lines — High100 psi≥112 psiTS T3.3-4
Steam Flow High (2 lines) coincident with Tavg Lo-Lo≥40% steam flow function; Tavg ≤543°F≥44% function; Tavg ≤541°FTS T3.3-4
Steam Flow High coincident with Steam Line Pressure Low600 psig steam line pressure≤579 psigTS T3.3-4

2. Containment Spray

Functional UnitTrip SetpointAllowable ValueSource
Manual InitiationN/AN/ATS T3.3-4
Automatic Actuation LogicN/AN/ATS T3.3-4
Containment Pressure — High-High15.0 psig≤16.0 psigTS T3.3-4

3. Containment Isolation

Functional UnitTrip SetpointAllowable ValueSource
Phase A — ManualN/AN/ATS T3.3-4
Phase A — From Safety InjectionN/A (auto on SI)N/ATS T3.3-4
Phase B — ManualN/AN/ATS T3.3-4
Phase B — Containment Pressure Hi-Hi15.0 psig≤16.0 psigTS T3.3-4
Containment Ventilation Isolation — ManualN/AN/ATS T3.3-4
Containment Ventilation Isolation — Gaseous Radioactivity HighPer Table 3.3-6Per Table 3.3-6TS T3.3-4

4. Steam Line Isolation

Functional UnitTrip SetpointAllowable ValueSource
ManualN/A (1/steam line)N/ATS T3.3-4
Automatic Actuation LogicN/AN/ATS T3.3-4
Containment Pressure — High-High15.0 psig≤16.0 psigTS T3.3-4
Steam Flow High (2 lines) coincident with Tavg Lo-Lo≥40% steam flow function; Tavg ≤543°F≥44% function; Tavg ≤541°FTS T3.3-4
Steam Flow High coincident with Steam Line Pressure Low600 psig steam line pressure≤579 psigTS T3.3-4

5. Turbine Trip and Feedwater Isolation

Functional UnitTrip SetpointAllowable ValueSource
Safety InjectionPer Function 1 abovePer Function 1TS T3.3-4
Automatic Actuation LogicN/AN/ATS T3.3-4
SG Water Level — High-High67% NR span (each SG)≤68% NR spanTS T3.3-4

6. Safeguards Equipment Control System (SEC)

See Functions 1 and 7 for all initiation functions.

7. Undervoltage — Vital Bus

Functional UnitTrip SetpointAllowable ValueSource
Loss of Voltage65% of bus voltage≥70% of bus voltageTS T3.3-4
Sustained Degraded Voltage94% of bus voltage for ≤15 sec≥94.6% for <13 secTS T3.3-4

8. Auxiliary Feedwater

Functional UnitTrip SetpointAllowable ValueSource
Automatic Actuation LogicN/AN/ATS T3.3-4
SG Water Level — Lo-Lo14.0% NR span (each SG)≥13.0% NR spanTS T3.3-4
Undervoltage — RCP70% RCP bus voltage≥65% RCP bus voltageTS T3.3-4
Safety InjectionSee Function 1See Function 1TS T3.3-4
Trip of Main Feedwater PumpN/AN/ATS T3.3-4
Station BlackoutSee Functions 6 and 7See Functions 6 and 7TS T3.3-4

9. Semiautomatic Transfer to Recirculation

Functional UnitTrip SetpointAllowable ValueSource
RWST Level — Low15.25 ft above instrument taps15.25 ±1 ft above tapsTS T3.3-4
Automatic Actuation LogicN/AN/ATS T3.3-4

ESF Channels and Actions (Table 3.3-3, Selected)

FunctionTotal ChannelsTo TripMin OPERABLEModesAction
SI — Manual2121,2,3,418
SI — Containment Pressure Hi3221,2,319
SI — PZR Pressure Low3221,2,319
SI — Differential Steam Pressure Hi3/line2/line2/line1,2,319
Containment Spray — Hi-Hi Pressure4231,2,316
Phase B Isolation — Hi-Hi Pressure4231,2,3,416
Steam Line Isolation — Hi-Hi Pressure4231,2,316
Turbine Trip/FW Isolation — Hi-Hi SG Level3/loop2/loop2/loop1,2,319
AFW — Lo-Lo SG Level (motor-driven)3/SG2/SG (any SG)2/SG1,2,319
AFW — Lo-Lo SG Level (turbine-driven)3/SG2/SG (any 2 SGs)2/SG1,2,319
RWST Level Low4231,2,316

ESF Interlocks

DesignationConditionSetpointFunction
P-112/3 PZR pressure channels≥1925 psigPrevents/defeats manual block of SI on low PZR pressure
P-12 (increasing Tavg)3/4 Tavg channels543°F (AV ≤545°F)Prevents/defeats manual block of SI on high steam flow. Causes steam line isolation on high steam flow. Affects steam dump blocks.
P-12 (decreasing Tavg)2/4 Tavg channels543°F (AV ≥541°F)Allows manual block of SI on high steam flow and low steam line pressure

(TS Table 3.3-3, Amendment No. 310)

Action Statements (Table 3.3-3)

ActionRequirement
131 channel inoperable: restore within 24 hrs or Hot Standby in 6 hrs + Cold Shutdown in 30 hrs. May bypass 1 channel for 4 hrs for testing.
141 channel inoperable: may proceed until next CFT, provided inoperable channel placed in trip within 72 hrs
161 channel inoperable: may proceed, place in bypass. May bypass 1 additional for 12 hrs testing.
17Less than min channels: may continue provided containment purge/exhaust valves maintained closed
181 channel inoperable: restore within 48 hrs or Hot Standby in 6 hrs + Cold Shutdown in 30 hrs
191 channel inoperable: place in trip within 72 hrs. May bypass for 12 hrs for testing of other channels.
201 channel inoperable: restore within 24 hrs or Hot Standby in 6 hrs + Hot Shutdown in 6 hrs. May bypass 1 for 4 hrs testing.
211 less than min channels: restore within 72 hrs
231 channel inoperable: restore within 48 hrs or Hot Standby in 6 hrs + Hot Shutdown in 6 hrs
Exam — 2020 Q88
TS 3.3.2.1 Action 16 applies to Hi-Hi Containment Pressure channels (CS, Phase B, steamline isolation): inoperable channel is placed in BYPASS (not tripped). This is because Containment Spray bistables are energized to actuate — placing an inoperable channel in the tripped condition would move it closer to actuation, increasing the risk of spurious Containment Spray. Contrast with Action 19 (most other ESF functions): inoperable channels are placed in TRIP because those bistables are de-energized to trip.
SI vs Containment Spray Pressure Setpoints
Safety Injection actuates on Hi containment pressure of 4.0 psig (2/3 coincidence). Containment Spray and Phase B isolation actuate on Hi-Hi containment pressure of 15.0 psig (2/4 coincidence). Steam Line Isolation also actuates on 15.0 psig Hi-Hi (2/4). These are different setpoints with different coincidence logic.
Motor-Driven vs Turbine-Driven AFW Actuation
Motor-driven AFW pumps start on Lo-Lo level in ANY 1 steam generator (2/3 per SG). Turbine-driven AFW pump starts on Lo-Lo level in ANY 2 steam generators (2/3 per SG in 2 SGs). The turbine-driven pump requires a more severe condition (2 SGs affected) before starting.
▶ Bases — 3/4.3.2 ESF Actuation Instrumentation
Bases — 3/4.3.2

OPERABILITY Requirements

The OPERABILITY of the ESFAS instrumentation ensures that: (1) the associated ESF action and/or reactor trip will be initiated when the parameter monitored by each channel or combination thereof exceeds its setpoint, (2) the specified coincidence logic and sufficient redundancy is maintained to permit a channel to be out of service for testing or maintenance consistent with maintaining an appropriate level of reliability, and (3) sufficient system functional capability is available from diverse parameters. The OPERABILITY of these systems is required to provide the overall reliability, redundancy, and diversity assumed available in the facility design for protection and mitigation of accident and transient conditions.

Coincidence Logic Rationale

The different coincidence logic requirements reflect a graded safety approach: Safety Injection actuates on 2/3 containment pressure Hi channels at 4.0 psig, while containment spray and Phase B isolation require 2/4 containment pressure Hi-Hi channels at 15.0 psig. The lower threshold and less restrictive coincidence for SI ensures early protective action, while the higher threshold and more restrictive coincidence for spray and Phase B prevents inadvertent actuation of more severe (and potentially damaging) functions.

Setpoint Methodology

The Trip Setpoints and Allowable Values incorporate all known uncertainties applicable to each channel, determined using the same ISA-S67.04-1982 methodology as the RTS. The actual nominal Trip Setpoint is more conservative than the Allowable Value to account for random measurement errors detectable by CHANNEL FUNCTIONAL TEST. Setpoints in accordance with the Allowable Value ensure the safety analyses demonstrating safety limits are not violated remain valid, provided the unit is operated within the LCOs at the onset of any design basis event.

Surveillance and Testing

The surveillance requirements are sufficient to demonstrate overall system functional capability comparable to original design standards. Surveillance and outage times are based on WCAP-10271 and supplements; completion times and bypass test times were increased per WCAP-14333-P-A, Rev. 1 and WCAP-15376-P-A, Rev. 1 using probabilistic risk analysis. Out of service times maintain an appropriate level of reliability.

Response Time Verification

Response time verification ensures the ESF actuation associated with each channel is completed within the time assumed in the safety analysis. The same methods as RTS apply: actual tests (sequential, overlapping, or total channel), or summation of allocated sensor response times with actual tests on the remainder. The Note 8 response times for feedwater isolation are based on WCAP-16503, Rev. 3 — SGFP trip and FIV closure are credited in containment analyses for LOCA and MSLB in case an FRV fails open.

(TS Bases B 3/4 3-1 through B 3/4 3-1a, Amendment Nos. 294, 306)


3/4.3.3 — Monitoring Instrumentation

Radiation Monitoring Instrumentation (3.3.3.1)

LCO 3.3.3.1
The radiation monitoring instrumentation channels shown in Table 3.3-6 shall be OPERABLE with their alarm/trip setpoints within the specified limits.

Applicability: As shown in Table 3.3-6

Actions:

  • a. Setpoint exceeding Table 3.3-6 value → adjust within 4 hours or declare inoperable
  • b. One or more channels inoperable → take ACTION shown in Table 3.3-6
  • c. Specification 3.0.3 is not applicable

SR 4.3.3.1: CHANNEL CHECK, SOURCE CHECK, CHANNEL CALIBRATION, and CHANNEL FUNCTIONAL TEST per Surveillance Frequency Control Program

Radiation Monitoring Channels (Table 3.3-6)

1. Area Monitors

InstrumentMin ChannelsApplicable ModesAlarm/Trip SetpointMeasurement RangeAction
Fuel Storage Area1*15 mR/hr10⁻¹–10⁴ mR/hr23

* With fuel in the storage pool or building.

2. Process Monitors

InstrumentMin ChannelsApplicable ModesAlarm/Trip SetpointMeasurement RangeAction
Containment Gaseous — Purge & PVR Isolation1#1, 2, 3, 4 & 5per ODCM Control 3.3.3.910¹–10⁶ cpm26
Containment Gaseous — RCS Leakage Detection11, 2, 3 & 4N/A10¹–10⁶ cpm24
Containment Air Particulate — RCS Leakage Detection11, 2, 3 & 4N/A10¹–10⁶ cpm24
Noble Gas — Medium Range Plant Vent11, 2, 3 & 43.0×10⁻² μCi/cm³ (Alarm only)10⁻³–10¹ μCi/cm³26
Noble Gas — High Range Plant Vent11, 2, 3 & 41.0×10² μCi/cm³ (Alarm only)10⁻¹–10⁵ μCi/cm³26
Noble Gas — Condenser Exhaust11, 2, 3 & 47.12×10⁴ cpm (Alarm only)1–10⁶ cpm26

# Plant vent noble gas monitor may also function in this capacity when purge/PVR isolation valves are open.

3. Control Room

InstrumentMin ChannelsApplicable ModesAlarm/Trip SetpointMeasurement RangeAction
Air Intake — Radiation Level2/Intake##**2.48×10³ cpm10¹–10⁷ cpm27, 28

## Control Room air intakes shared between Unit 1 and 2. ** ALL MODES and during movement of irradiated fuel assemblies and during CORE ALTERATIONS.

Radiation Monitoring Action Statements (Table 3.3-6)

ActionRequirement
23Less than min channels: perform area surveys with portable monitoring at least once per 24 hours
24Less than min channels: comply with ACTION requirements of Specification 3.4.7.1
26Less than min channels: initiate preplanned alternate method within 72 hours; restore within 7 days or submit Special Report within 14 days
27One less than min channels: restore within 7 days or initiate CREACS in pressurization/recirculation mode. Suspend CORE ALTERATIONS and irradiated fuel movement during recirculation mode.
28No channels OPERABLE in a CR air intake: immediately initiate CREACS in pressurization/recirculation mode. Suspend CORE ALTERATIONS and irradiated fuel movement during recirculation mode.

(Table 3.3-6, Amendment Nos. 245, 253, 278)

Exam — 2019 Q96
LCO 3.3.3.1 Table 3.3-6 application during Containment Vacuum Relief (SRO question): 2R12A is the credited monitor for both 2.a.1.a (Containment Gaseous Activity — Purge & PVR Isolation) and 2.a.1.b (Containment Gaseous Activity — RCS Leak Detection). During a Containment Vacuum Relief, 2R41 (Plant Vent Noble Gas) can also be used to meet 2.a.1.a requirements (per TS Bases). With 2R12A AND 2R41D both failed: (1) 2.a.1.b requirement is NOT met → Action 24, and (2) 2.a.1.a requirement is NOT met (2R12A failed, and 2R41D which was serving as alternate is also failed) → Action 26. Both actions required. Trap: candidates may think redundant monitors (2R12B/C or 2R41A/B) satisfy the requirement, but each Table 3.3-6 line item has its own minimum channel requirements. Multiple R12 or R41 channels exist but serve different functions per the bases.
▶ Bases — 3/4.3.3.1 Radiation Monitoring
Bases — 3/4.3.3.1

The OPERABILITY of the radiation monitoring channels ensures that: (1) radiation levels are continually measured in the areas served by the individual channels, and (2) the alarm or automatic action is initiated when the radiation level trip setpoint is exceeded.

For the postulated Fuel Handling Accident, revised dose calculations using 10 CFR 50.67 and Regulatory Guide 1.183 (Alternative Source Term) do not take credit for automatic containment purge isolation, allowing continuous monitoring of containment activity until containment closure is achieved. If required, containment purge isolation can be initiated manually from the control room.

“Immediate action(s)” in accordance with LCO Action Statements means the required action should be pursued without delay and in a controlled manner.

(TS Bases B 3/4 3-2, TSBC S2013-057 and Amendment No. 301)


Remote Shutdown Instrumentation (3.3.3.5)

LCO 3.3.3.5
The remote shutdown monitoring instrumentation channels shown in Table 3.3-9 shall be OPERABLE with readouts displayed external to the control room.

Applicability: MODES 1, 2, and 3

Action: Restore inoperable channel within 7 days or be in HOT SHUTDOWN within 12 hours.

SR 4.3.3.5: CHANNEL CHECK and CHANNEL CALIBRATION per Surveillance Frequency Control Program

Remote Shutdown Channels (Table 3.3-9)

InstrumentReadout LocationMeasurement RangeMin Channels OPERABLE
Pressurizer PressureHot Shutdown Panel 2131700–2500 psig1
Pressurizer LevelHot Shutdown Panel 2130–100%1
Steam Generator PressureHot Shutdown Panel 2130–1200 psig1/steam generator
Steam Generator LevelHot Shutdown Panel 2130–100%1/steam generator

(Table 3.3-9, Amendment No. 282)

▶ Bases — 3/4.3.3.5 Remote Shutdown Instrumentation
Bases — 3/4.3.3.5

The OPERABILITY of the remote shutdown instrumentation ensures that sufficient capability is available to permit shutdown and maintenance of HOT STANDBY from locations outside the control room. This capability is required in the event control room habitability is lost and is consistent with General Design Criterion 19 of 10 CFR 50.

(TS Bases B 3/4 3-3, Amendment No. 301)


Accident Monitoring Instrumentation (3.3.3.7)

LCO 3.3.3.7
The accident monitoring instrumentation channels shown in Table 3.3-11 shall be OPERABLE.

Applicability: MODES 1, 2, and 3

Action: As shown in Table 3.3-11. Separate Condition entry is allowed for each Function.

SR 4.3.3.7: CHANNEL CHECK, CHANNEL CALIBRATION, and CHANNEL FUNCTIONAL TEST per Surveillance Frequency Control Program unless otherwise noted in Table 4.3-11

Accident Monitoring Channels (Table 3.3-11)

#InstrumentRequired ChannelsMin ChannelsAction
1RCS Outlet Temp — T_HOT (Wide Range)211, 2
2RCS Inlet Temp — T_COLD (Wide Range)211, 2
3RCS Pressure (Wide Range)211, 2
4Pressurizer Water Level211, 2
5Steam Line Pressure2/SG1/SG1, 2
6SG Water Level (Narrow Range)2/SG1/SG1, 2
7SG Water Level (Wide Range)4 (1/SG)3 (1/SG)1, 2
8RWST Water Level211, 2
10Auxiliary Feedwater Flow Rate4 (1/SG)3 (1/SG)4, 6
16Containment Pressure — Wide Range217, 2
17Containment Water Level — Wide Range217, 2
18Core Exit Thermocouples4/core quadrant2/core quadrant1, 2
19Reactor Vessel Level Instrumentation System (RVLIS)218, 9
20Containment High Range Accident Radiation Monitor2210
21Main Steamline Discharge (Safety Valves & Atmospheric Steam Dumps) Monitor1/MS Line1/MS Line10
22Wide Range Neutron Flux Monitors211, 2
23AFW Storage Tank (CST) Water Level211, 2
24Containment Isolation Valve Position Indication2 per penetration flow path (a)(b)1/valve (c)1, 2

(a) Not required for isolation valves whose associated penetration is isolated by at least one closed and deactivated valve, closed manual valve, blind flange, or check valve with flow secured. (b) Only one position indication channel is required for penetration flow paths with only one installed control room indication channel. (c) Action 2 not required for penetration flow paths with only one installed control room indication channel.

Accident Monitoring Action Statements (Table 3.3-11)

ActionRequirement
1Less than Required channels: restore within 30 days or submit special report per Spec 6.9.4
2Less than Minimum channels: restore within 7 days or HOT STANDBY in 6 hrs + HOT SHUTDOWN in 6 hrs
4One less than Required (AFW Flow): may proceed if OPERABLE SG Wide Range Level channel available as alternate for that SG; otherwise restore within 30 days or submit special report
6Less than Minimum channels: restore within 7 days or HOT STANDBY in 6 hrs + HOT SHUTDOWN in 6 hrs
7One less than Required (Containment instruments): may proceed until next CHANNEL CALIBRATION (performed upon next entry into MODE 5, COLD SHUTDOWN)
8One RVLIS channel inoperable: restore within 30 days or submit special report per Spec 6.9.4
9Both RVLIS channels inoperable: restore one within 7 days or submit special report per Spec 6.9.4
10Less than min channels: initiate preplanned alternate method within 72 hours; restore within 7 days or submit Special Report within 14 days

Accident Monitoring Surveillance (Table 4.3-11)

InstrumentChannel CheckChannel CalibrationChannel Functional Test
Items 1–8 (RCS temps, pressure, PZR level, SG level/pressure, RWST level)Per SFCPPer SFCPN.A.
AFW Flow RateS/U*Per SFCPN.A.
Containment Pressure/Water Level (Wide Range)Per SFCPPer SFCPN.A.
Core Exit ThermocouplesPer SFCPPer SFCPN.A.
RVLISPer SFCPPer SFCPN.A.
Containment High Range Radiation MonitorPer SFCPPer SFCPPer SFCP
Main Steamline Discharge MonitorPer SFCPPer SFCPPer SFCP
Wide Range Neutron Flux MonitorsPer SFCPPer SFCPN.A.
AFW Storage Tank (CST) LevelPer SFCPPer SFCPN.A.
Containment Isolation Valve PositionPer SFCPPer SFCPN.A.

* AFW System is used on each startup and flow rate indication is verified at that time.

(Table 3.3-11, Table 4.3-11, Amendment No. 301)

▶ Bases — 3/4.3.3.7 Accident Monitoring Instrumentation
Bases — 3/4.3.3.7

The OPERABILITY of the accident monitoring instrumentation ensures that sufficient information is available on selected plant parameters to monitor and assess these variables following an accident. This capability is consistent with the recommendations of Regulatory Guide 1.97, “Instrumentation for Light-Water-Cooled Nuclear Power Plants to Assess Plant Conditions During and Following an Accident” (December 1975) and NUREG-0578, “TMI-2 Lessons Learned Task Force Status Report and Short-Term Recommendations.”

The Wide Range Neutron Flux Monitors are the Gamma-Metrics Post-Accident Neutron Monitors.

(TS Bases B 3/4 3-3, Amendment No. 301)

Exam — 2019 Q47
Per LCO 3.3.3.7, 2PT-403 (RCS Narrow Range Pressure) and 2PT-405 (RCS Wide Range Pressure) ARE credited as accident monitoring instrumentation. They provide input to BOTH the Pressurizer Overpressure Protection System (POPS) and to the RVLIS Electronics Cabinets. Trap: POPS is not their only function — they also feed RVLIS.

Radioactive Liquid Effluent Monitoring Instrumentation (3.3.3.8)

LCO 3.3.3.8
The radioactive liquid effluent monitoring instrumentation channels shown in Table 3.3-12 shall be OPERABLE to ensure that the limits of ODCM Control 3.11.1.1 are not exceeded.

Applicability: At all times

Actions:

  • b. Less than min channels → take ACTION in Table 3.3-12. Exert best efforts to return within 30 days.
  • c. Specification 3.0.3 is not applicable.

SR 4.3.3.8: CHANNEL CHECK, SOURCE CHECK, CHANNEL CALIBRATION, and CHANNEL FUNCTIONAL TEST per Surveillance Frequency Control Program

Radioactive Liquid Effluent Channels (Table 3.3-12)

InstrumentMin Channels OPERABLEAction
Tank Level Indicating Devices — Temporary Outside Storage Tanks (as required)130

Action 30: Less than min channels: liquid additions may continue for up to 30 days provided tank liquid level is estimated during all liquid additions.

Surveillance (Table 4.3-12): Channel Check daily during liquid additions to tank. If tank level indication not provided, verification by visual inspection. Channel Calibration per SFCP.

(Table 3.3-12, Table 4.3-12, Amendment Nos. 215, 282)

▶ Bases — 3/4.3.3.8 Radioactive Liquid Effluent Monitoring
Bases — 3/4.3.3.8

The purpose of tank level indicating devices is to assure the detection and control of leaks that, if not controlled, could potentially result in the transport of radioactive materials to unrestricted areas.

(TS Bases B 3/4 3-3a, Amendment No. 323)


Power Distribution Monitoring System (3.3.3.14)

LCO 3.3.3.14
The Power Distribution Monitoring System (PDMS) shall be OPERABLE with: (a) minimum plant inputs per Table 3.3-14, (b) Core Exit Thermocouples meeting minimum coverage criteria, and (c) an installed PDMS calibration satisfying accuracy criteria.

Applicability: MODE 1, above 25% RTP

Action: Correct the deficient operability condition, or declare PDMS inoperable and use incore movable detector system for required core power distribution measurements. Increase measured peaking factors using COLR values for PDMS inoperable condition. Specification 3.0.3 is not applicable.

PDMS Operability Criteria:

  • a. Plant Inputs — minimum valid inputs per Table 3.3-14
  • b. Core Exit Thermocouples:
    • At least 25% operable T/C with at least 2 T/C per quadrant, AND
    • T/C pattern has coverage of all interior fuel assemblies within a chess knight’s move from a responding calibrated T/C; OR
    • At least 25% operable T/C with at least 2 T/C per quadrant, AND installed PDMS calibration within last 31 EFPD
    • T/C temperatures calibrated via cross-calibration with loop RTDs using T/C flow mixing factors
  • c. Installed Calibration:
    • Initial calibration each cycle: ≥75% of incore movable detector thimbles at >25% RTP
    • Subsequent calibrations: ≥50% of incore movable detector thimbles
    • Minimum 2 detector thimbles per core quadrant

PDMS Required Plant Inputs (Table 3.3-14)

Plant InputAvailable InputsMin Valid InputsApplicable Modes
Control Bank Position (a)441 (>25% RTP)
T_cold421 (>25% RTP)
Reactor Power Level (b)311 (>25% RTP)
NIS Power Range Excore Detector Section Signals (d)861 (>25% RTP)

(a) From valid Demand Position or average of valid individual RCCA position indications for all RCCAs in the Control Bank. (b) From secondary calorimetric, average NIS Power Range Detector Power, or average RCS Loop Delta-T. (d) Upper and lower detector section signals per Power Range Channel; minimum 3 OPERABLE channels required.

Surveillance Requirements:

  • 4.3.3.14.1: Operability criteria verified prior to acceptance of PDMS core power distribution measurement results
  • 4.3.3.14.2: Calibration required per Surveillance Frequency Control Program when minimum T/C number and coverage criteria are satisfied

(Table 3.3-14, Amendment Nos. 218, 282)

▶ Bases — 3/4.3.3.14 Power Distribution Monitoring System (PDMS)
Bases — 3/4.3.3.14

The PDMS provides continuous core power distribution measurement using a highly accurate 3-D nodal simulation of the current reactor power distribution. The simulated distribution is continuously adjusted by nodal and thermocouple calibration factors derived from incore power distribution measurements using the incore movable detectors. Nodal calibration factors are updated in accordance with the Surveillance Frequency Control Program.

Between calibrations, the fidelity of the measured power distribution is maintained by adjusting the calibrated distribution using continuously input plant and core condition data. This data is cross-checked using redundant information.

PDMS Operability Requirements — Four Categories:

  1. Assure an adequate number of operable critical sensors
  2. Assure sufficiently accurate calibration of these sensors
  3. Assure an adequate calibration database regarding the number of data sets
  4. Assure the overall accuracy of the calibration

Minimum Required Inputs:

  1. Control Bank Positions
  2. At least 50% of the cold leg temperatures
  3. At least 75% of the power range excore detector channel signals (top and bottom detector sections)
  4. Reactor Power Level
  5. A minimum number and distribution of operable core exit thermocouples
  6. A minimum number and distribution of measured fuel assembly power distribution information from incore movable detectors

Thermocouple calibration is accomplished in two parts: (1) a sensor-specific correction to K-type thermocouple indications based on cross-calibration to average RCS temperature measured via RTDs under isothermal conditions, and (2) generation of thermocouple flow mixing factors that cause the radial power distribution measured via thermocouples to agree with the distribution from a full core flux map using incore movable detectors. The PDMS uses NIS Power Range excore detectors for axial power distribution information, averaging data from the four detectors and eliminating bad data.

(TS Bases B 3/4 3-4 through B 3/4 3-5, Amendment No. 282)

View Tech Spec PDF (61 pages — full tables) | View Bases PDF

Exam — 2018 Q82
LCO 3.3.1.1 action for PZR Level Channel failure: with 2LT-459 (Channel I PZR Level) failed high at 100% power, the channel must be placed in the tripped condition within 6 hours (not 1 hour). PZR Level — High is a 3-channel trip function (Table 3.3-1) with 2/3 coincidence.
Exam — 2018 Q89
LCO 3.3.3.1 (Radiation Monitoring Instrumentation) / Table 3.3-6 analysis: R12A is the credited monitor for BOTH Table 3.3-6 item 2.a.1.a (Containment Gaseous Activity — Purge & Pressure Vacuum Relief Isolation) AND 2.a.1.b (Containment Gaseous Activity — RCS Leak Detection). During containment vacuum relief operations, R41 (2R41A, B, D) can serve as alternate monitor for item 2.a.1.a only. With R12A failed: LCO NOT met → Action 24 ONLY (R41 satisfies 2.a.1.a, but nothing replaces R12A for 2.a.1.b → Action 24). Trap: candidates may think both Actions 24 AND 26 are required (forgetting R41 can substitute for 2.a.1.a during vacuum relief), or that LCO is met with R12A failed (it is not).

Connections