procedures > S2.OP-AR.ZZ-0001 — Overhead Annunciators Window A

S2.OP-AR.ZZ-0001 — Overhead Annunciators Window A

⚠️ DRAFT

S2.OP-AR.ZZ-0001 — Overhead Annunciators Window A

Purpose

Alarm response procedure for Unit 2 overhead annunciator panel Window A, covering alarms such as RMS HI RAD OR TRBL (OHA A-6).

Key Actions / Information

Exam — 2022 Q51
OHA A-6 (RMS HI RAD OR TRBL): When 2R1B-1 (Control Room Intake Radiation Monitor Channel 1) goes into ALARM, both units' CAV systems should automatically actuate to AP (Accident Pressurize) Mode. If automatic actuation fails, manually initiate AP Mode from Unit 2 (the unit with the high radiation signal). Manually actuating from Unit 1 would open Unit 2 intake dampers, which is the wrong response since Unit 2 is the unit with the potential radiological release.
Exam — 2020 Q25
OHA A-6 (RMS HI RAD OR TRBL) due to 2R41D Plant Vent Effluent: during SI termination (EOP-TRIP-3), this alarm in combination with C-34 (22 RHR SUMP OVRFLO) and RHR sump pump starts indicates a LOCA outside containment. Leads to EOP-TRIP-3 CAS → EOP-LOCA-1 → EOP-LOCA-6.
Exam — 2019 Q36
OHA A-6 (RMS HI RAD OR TRBL) due to 2R9 (Fuel Storage Area Monitor) alarm: both FHB Exhaust Fans receive auto start signal, 21 HEPA ONLY Filter Unit isolates, HEPA 22 PLUS CHAR automatically aligns.