Purpose

Provides direction for recording control room logs during Modes 1-4, including channel checks for rod position indication, IRPI, and plant computer comparisons.

Key Actions / Information

Exam — 2023 Q56
For Control Rod Counter channel checks, either the Group Demand Counter or Plant Computer will satisfy the surveillance for Group 1 only. Only the Group 1 Demand Steps input into the Plant Computer. TS 3.1.3.2.1.b bases states: "either the control console group 1 demand step counter or the plant computer 'bank step' display is sufficient to comply with this specification for group 1 rod position."
JPM — 2018 RO-A2
Control room log 1830 readings: Tavg Channel Check for all 4 RC loops (must be within 3 degrees F, S/R 4.3.2.1.1 Modes 1-3) and OTDT setpoint check per REM FIGURE 5 (A-D). 2CC1 console OTDT readings compared against REM setpoint band. Loop 24 OTDT setpoint of 72 deg F is outside the REM FIGURE 5D setpoint band — record UNSAT or red-circle and notify CRS.