Exams > 2023 JPM IP-i — Start the SBO Air Compressor IAW AB.LOOP-1

2023 JPM IP-i — Start the SBO Air Compressor IAW AB.LOOP-1

⚠️ DRAFT
JPM IP-i — Start the SBO Air Compressor IAW AB.LOOP-1 In-Plant | RO/SRO | 056 AA1.37 (3.4)
Location: In-Plant — SBO Compressor Building (outside RCA, requires L-3 key)
Time-Critical: No
Alternate Path: No
Estimated Time: 15 minutes

Initial Conditions:
- Both Salem Units have tripped due to a loss of off-site power. Equipment problems have resulted in NO Emergency Control Air Compressors (ECACs) running.

Initiating Cue:
- The Unit 2 CRS has directed you to start the Station Blackout Compressor (SBO) IAW SC.OP-SO.CA-0001, SBO Diesel Control Air Compressor, starting with Step 5.1.3.
- The Component Off Normal and Off Normal Tagged review has been performed SAT.
- It is NOT the summer operating period.
- The inspection covers have already been removed, Step 5.1.1 was performed SAT, and the inspection covers replaced IAW Step 5.1.2
Task Standard:
The task is satisfactorily met when the applicant starts the SBO Diesel Control Air Compressor IAW step 5.1.10 of SC.OP-SO.CA-0001, aligns the discharge to the air headers IAW steps 5.1.13 thru 5.1.15 of SC.OP-SO.CA-0001, and loads the compressor IAW step 5.1.16 of SC.OP-SO.CA-0001.
▶ Show Critical Steps & Key Actions
Step Critical Element Standard
5.1.3 OPEN both Engine intake louvers (located outside building on west wall) Locates louvers and demonstrates how to open.
5.1.4 OPEN 1CA1920, BLACKOUT AIR COMPRESSOR DRAIN VALVE, drain water, then CLOSE Locates 1CA1920 and describes how to open, including removing drain cap.
5.1.5 OPEN 2FZSBO10, BATTERY CHARGER, breaker Locates 2FZSBO10 in Panel 2FZSBO, SBO Compressor Bldg Distribution Panel, and simulates opening.
5.1.6 PLACE SBO Control Air Dryer switch in ON position Locates switch, simulates turning to ON. Control Air On light illuminates.
5.1.7 RECORD Engine Hourmeter reading on Attachment 1 and in log book Locates Engine Hourmeter (1XA16993) inside engine control panel and logbook on side of panel 2FZSBO.
5.1.8 PLACE UNLOADER VALVE selector switch in START position Locates switch and ensures in START position (normally in Start when engine is shutdown).
5.1.9 * PRESS AND HOLD BY-PASS VALVE pushbutton Locates BY-PASS VALVE pushbutton in control panel and simulates depressing AND holding depressed.
5.1.10 * PLACE SBO-IGN-SWT, ENGINE IGNITION SWITCH in START until engine starts, then RELEASE to RUN While keeping Bypass Valve pushbutton depressed, simulates placing SBO-IGN-SWT in START. After engine starts, releases to RUN. Must NOT release BY-PASS VALVE pushbutton until oil pressure is verified >15 psig in next step.
5.1.11 * When engine oil pressure is >15 psig, RELEASE BY-PASS VALVE pushbutton Identifies oil pressure reading on gauge inside control panel. After cue (40 psig), releases BY-PASS VALVE pushbutton. Releasing early (without checking oil pressure) causes the engine to stop.
5.1.12 ALLOW engine to run for 5 minutes to warm up N/A — wait for warm-up period.
5.1.13 * OPEN 1CA1913 SBO COMPRESSOR DISCHARGE VALVE Locates and describes opening 1CA1913 to pressurize Control Air header.
5.1.14 * OPEN 1CA1886, BLACKOUT AIR COMPRESSOR ISOLATION Locates and describes opening 1CA1886 (near entrance to Service Building past U2 mixing bottle).
5.1.15 * OPEN 2CA584, YARD CONTROL AIR SUPPLY VALVE Locates and describes opening 2CA584 to pressurize Aux. Building 1A and 2A Control Air headers (near entrance to Service Building past U2 mixing bottle).
5.1.16 * PLACE UNLOADER VALVE selector switch in RUN position Returns to SBO Compressor Building and places UNLOADER VALVE selector switch in RUN to load the compressor.
Key Decision Point:
Steps 5.1.10 and 5.1.11 are the discriminating steps — the applicant must keep the BY-PASS VALVE pushbutton depressed while starting the engine with SBO-IGN-SWT, then verify oil pressure >15 psig BEFORE releasing the bypass valve pushbutton. Releasing the bypass valve early (without checking oil pressure) will cause the engine to stop.
Ref: SC.OP-SO.CA-0001 (R14) | Task: N1150140501 | K/A: 056 AA1.37 — Ability to operate and/or monitor the following as they apply to Loss of Offsite Power: Instrument Air | Source: Bank | View JPM PDF